MS Miayiri LEV-P Series LPG Emergency Shut-off Valve JIS20K RF SCPH2
Brand: MS Miyairi
Models: LEV-P, LEV-PE, LEV-PA, LEV-PAEHOT
Nominal Diameter: 20A, 25A, 40A, 50A, 80A
Applicable Fluids: LPG, Ammonia
Design Pressure: 2.4 MPa
Design Temperature: -5 to 70°C
Hydrostatic Test Pressure: 3.9 MPa
Pneumatic Seal Test Pressure: 2.4 MPa
Flange Connection Standard: JIS 20K RF
Valve Body Material: SCPH2

Emergency shut-off valve designed for high-pressure gas equipment. Normally, the valve remains open under the action of a hydraulic or pneumatic cylinder; during emergencies, the valve closes by releasing hydraulic or pneumatic pressure. Additionally, in the event of a fire, a fusible alloy melts, causing the valve to close automatically.
Pneumatic Emergency Shut-Off Valve
Model: LEV-PA, LEV-PAE
Type: Pneumatic
Pressurized Medium: Air
Operating Pressure: 0.3–0.5 MPa
Fusible Alloy Melting Temperature: 75°C
Hydraulic Emergency Shut-Off Valve
Model: LEV-P, LEV-PE
Type: Hydraulic
Pressurized Medium: Oil
Operating Pressure: 2.9–4.9 MPa
Fusible Alloy Melting Temperature: 75°C
Valve Body Specifications:
Brand: MS Miyairi
Models: LEV-P, LEV-PE, LEV-PA, LEV-PAE
Nominal Diameter: 20A, 25A, 40A, 50A, 80A
Applicable Fluids: LPG, Ammonia
Design Pressure: 2.4 MPa
Design Temperature: -5 to 70°C
Hydrostatic Test Pressure: 3.9 MPa
Pneumatic Seal Test Pressure: 2.4 MPa
Flange Connection Standard: JIS 20K RF
Valve Body Material: SCPH2
Features:
(1) Composed of a globe valve and cylinder. When hydraulic or pneumatic pressure is applied to the cylinder, the valve opens. Upon pressure release, the disc is loaded by an internal spring and upstream fluid pressure, ensuring movement toward the closed position and maintaining tight sealing.
(2) Pilot-operated design: when opening via hydraulic or pneumatic pressure, the pilot valve opens first, reducing the differential pressure between upstream and downstream, allowing the main valve to open. This enables a compact, lightweight cylinder.
(3) The cylinder section is separated from the valve bonnet, allowing replacement of cylinder wear parts without draining pipeline fluid.
(4) Equipped with a visual open/close indicator for clear status confirmation.
(5) In case of fire, the fusible alloy melts and the valve closes automatically.